Carrier Mini-Split: Fan motor check (indoor DC motor and outdoor DC motor)
Fan motor check (indoor DC motor and outdoor DC motor) on a Carrier mini-split: Checks for DC fan motors. Indoor motors have the control chip inside the motor. Outdoor motors have the control chip on the outdoor PCB.
Applies to: D5FSOAH indoor and outdoor fan motors
How to fix fan motor check (indoor dc motor and outdoor dc motor): step by step
- Indoor DC motor: with power on and the unit in standby, measure voltage at pin 1 to pin 3 and pin 4 to pin 3 on the fan motor connector. If not in range (see table), replace the PCB.
- Outdoor DC motor: release the UVW connector. Measure resistance U-V, U-W and V-W.
- If the three resistances are not equal, replace the fan motor.
- If they are equal, replace the outdoor PCB.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSOAH06XAKD5FSOAH12XAKD5FSOAH18XAK
Source: D5FSOAH service manual, p. 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.