Cut, deburr, flare and connect refrigerant pipes on a Carrier mini-split: Prepare the line set and connect it to the indoor unit first, then the outdoor unit.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Refrigerant line set installation

Common causes of cut, deburr, flare and connect refrigerant pipes

  • Oblique, rough or warped cuts, and burrs left in the pipe, cause leaks.

How to fix cut, deburr, flare and connect refrigerant pipes: step by step

  1. Measure the run between the indoor and outdoor units and cut the pipe a little longer than that.
  2. Cut at a true 90° angle without deforming the pipe.
  3. Ream or deburr the cut end fully. Hold the pipe pointing down so burrs do not fall in.
  4. Seal the pipe ends with PVC tape during handling.
  5. Slip the flare nuts on in the correct direction before flaring. They cannot be turned after flaring.
  6. Flare the pipe. The pipe end must stick out beyond the flare form. Check for cracks and an even flare.
  7. Lightly oil the flared surfaces with refrigeration oil.
  8. Connect the low-pressure line first, then the high-pressure line.
  9. Hand-tighten the nut, then torque it to the value in the torque table.
  10. Bend tubing no more than 90° and no more than 3 times, keeping the bend radius at least 3.9 in (10 mm).
  11. Keep the branch pipe horizontal. More than 10° of tilt can cause malfunction.
  12. Insulate the gas and liquid lines to prevent condensation.
  13. Keep the interconnect cable away from the copper tube.
  14. Do not connect the line set until both units are installed.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Mini-Split codes

Source: Carrier D5FCFA installation manual, p. 20-21. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.