Carrier Mini-Split: Cut, deburr and flare refrigerant pipe
Cut, deburr and flare refrigerant pipe on a Carrier mini-split: Prepare the copper line set for flare connections.
Applies to: Field-prepared refrigerant pipe ends
How to fix cut, deburr and flare refrigerant pipe: step by step
- Measure the distance between the indoor and outdoor units.
- Cut the pipe slightly longer than that distance with a pipe cutter, keeping the cut square at 90°.
- Deburr the cut end with a reamer or deburring tool, holding the pipe pointed downward so chips do not fall in.
- Seal the pipe ends with PVC tape until flaring.
- Slide flare nuts onto both ends facing the correct direction. Flaring makes this impossible to change later.
- Remove the tape, clamp the flare block so the pipe extends past the form, and turn the flaring tool clockwise until fully flared.
- Check the flare for cracks and even shape. Confirm it matches the dimensions in the flare table.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Source: D5FSAA and D5FLAA installation instructions, p. 24-25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.