Carrier Mini-Split: Connect refrigerant pipes and insulate
Connect refrigerant pipes and insulate on a Carrier mini-split: Connect the low-pressure line first, then the high-pressure line. Do not let any other gas or substance enter the unit.
Applies to: Refrigerant connections, 6K-18K
How to fix connect refrigerant pipes and insulate: step by step
- Connect the copper pipes to the indoor unit first, then to the outdoor unit.
- Apply a thin coat of refrigeration oil to the flared ends.
- Align the centre of the two pipes, then tighten the flare nut by hand.
- Hold the unit tubing nut with a spanner and tighten the flare nut with a torque wrench to the value in the torque table.
- Bend the tubing gently at the middle. Do not exceed 90° or bend it more than 3 times. Minimum bend radius is 3.9 in (100 mm).
- Wrap the power cable, signal cable and piping together with binding tape. Do not twist the signal cable with other wiring.
- Thread the piping through the wall and connect it to the outdoor unit.
- Insulate all piping, including the outdoor unit valves. Bare pipe can cause burns or frostbite.
- Fix the water receiver (from the accessories box) to the indoor unit with a screw.
- Open the outdoor stop valves to let refrigerant flow between units.
- Check for leaks after installation. If a leak is found, ventilate the area immediately and evacuate the system.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Source: D5FSOAH installation instructions, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.