Carrier Mini-Split: Compressor winding check
Compressor winding check on a Carrier mini-split: Reference winding resistances for the inverter compressor models. Readings in the text are listed without a reliable column-to-row match, so verify against the manual figure before judging a winding. Values listed: 1.86 ohm, 0.75 ohm, 1.04 ohm, 0.65 ohm, 0.295 ohm. Compressor models: KSN140D58UFZ, KTF250D22UMT, KTM240D46UKT2, KTF310D43UMT, MTH550UKPC8FU. Winding pairs: Blue-Red, Blue-Black, Red-Black. Values are for reference only and may vary.
Applies to: D5FSFAH outdoor unit compressor
How to fix compressor winding check: step by step
- Disconnect the compressor power cord from the outdoor PCB.
- Measure the resistance of each winding with a multimeter.
- Compare each reading with the matching compressor model in Table 8 and Tables 9 to 12.
- Replace the compressor if the readings are out of range.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSFAH09XAKD5FSFAH12XAKD5FSFAH16XAK
Source: Carrier D5FSFAH service manual, p. 37. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.