Carrier Mini-Split: Charging a flammable refrigerant system
Charging a flammable refrigerant system on a Carrier mini-split: Charge carefully and check for leaks before handover.
Applies to: Charging R454B systems
How to fix charging a flammable refrigerant system: step by step
- Use only tools suited to flammable refrigerants.
- Keep charging hoses as short as possible.
- Keep cylinders upright.
- Earth the system before charging.
- Do not overfill the system.
- Pressure test with oxygen-free nitrogen before recharging.
- Leak test after charging and before commissioning, then again before leaving the site.
- Label the system after charging.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
45MBCAQ12XA3D5FLCAH36XAKD5FLCAH48XAKD5FSCAH12XAKD5FSCAH18XAKD5FSCAH24XAK
Source: D5FSCAH / D5FLCAH service manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.