Daikin Heat Pump: Reversing valve will not shift
Reversing valve will not shift on a Daikin heat pump: Electrical and mechanical checks for a stuck reversing valve.
Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)
How to fix reversing valve will not shift: step by step
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- In cooling, check for 24 V at the solenoid. No voltage: check the thermostat O circuit and wiring.
- With voltage there, pull the coil. You should feel slight pull and hear a click. No click = stuck pilot plunger.
- Check the solenoid coil for continuity. Open coil: replace the coil.
- Try raising head pressure (block the outdoor fan discharge in cooling) and switch between cool and heat to free the slide.
- By temperature: the discharge line should match the line after the valve, and true suction should match the suction line after the valve. A 4 degree difference means the valve is leaking. High suction pressure and a warm suction line can mean it is stuck half way.
- Coil good and 24 V present but the valve still will not move: replace the valve.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Models
DH4SEA**10AADH4SQA**10AADH5SEA**10AA
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting the Reversing Valve p.31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.