Updated · by Aurora Star Tech Inc.

FIT communication error: network check on a Daikin heat pump: Steps to clear a network communication code on a FIT system.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Common causes of fit communication error: network check

  • Miswired terminal 1 / 2
  • Damaged or broken communication cable
  • Wrong termination for the cable run

How to fix fit communication error: network check: step by step

  1. Kill power at the disconnect before opening the control box or touching wiring.
  2. Check the low voltage wiring against the install instructions. Terminals 1 and 2 swapped is the common mistake.
  3. Look for broken wires at terminals and inside wire nuts, and damage on the cable between units.
  4. Do a continuity check on each wire. Replace the cable if needed.
  5. Do not land more than two wires on one terminal; they come loose.
  6. Try the termination dip switch combinations: DS1 (switches 1 and 2) on the outdoor board and DS7 on the indoor board if it has one. Factory setting is both ON on both boards. Try the four combinations one at a time and power up after each change.
  7. Press LEARN about 5 seconds to reset the network.
  8. Read the red and green network LEDs on the boards to narrow it down.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Models

DH6VS*181DH6VS*241DH6VS*301DH6VS*361DH6VS*421DH6VS*481DH6VS*601DH7VSA2410DH7VSA3610DH7VSA4210DH7VSA4810

Source: Daikin 3P761829-1B FIT outdoor unit installation & service reference, Network Troubleshooting p.47 (printed page). Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.