Trane General: XR724 thermostat screen is blank
XR724 thermostat screen is blank on a Trane general: The XR724 has no power. It runs on 24 VAC from the equipment, so it needs both R and C wired. No C wire = dead screen.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
Common causes of xr724 thermostat screen is blank
- No 24 VAC between R and C at the thermostat
- Transformer not putting out 24 VAC
- Broken, shorted or loose thermostat wire
How to fix xr724 thermostat screen is blank: step by step
- Check that the furnace or air handler has power.
- At the thermostat sub-base, measure R to C. You should see about 24 VAC.
- No voltage there: measure R to C at the equipment board. If it is good at the board, the wire run is open; check each conductor end to end.
- No voltage at the board: check the transformer output. A shorted thermostat wire can also kill the 24 V, so check the wire run too.
- Make sure a C wire is actually connected at both ends. The XR724 will not run without it.
If the unit shows an error code, look it up: Trane General codes
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.