Trane General: Room goes past setpoint in cooling (XR724)
Room goes past setpoint in cooling (XR724) on a Trane general: The house cools below the cool setpoint before the system shuts off. Usually this is a setting, not a fault.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
Common causes of room goes past setpoint in cooling (xr724)
- Cooling delta Off is set to a negative number
- Cooling overshoot is on and indoor RH is above the cooling RH target, so the control keeps cooling to dry the house
- Minimum compressor on time has not run out yet
How to fix room goes past setpoint in cooling (xr724): step by step
- Check indoor RH against the cooling RH target. If RH is higher, the overshoot is doing its job.
- If the customer does not want it: turn cooling overshoot off, or raise the cooling RH target.
- Check the cooling delta Off. Set it to 0 if they do not want the room to go below setpoint.
- If it is the minimum on time, change Control Response under Installer Settings > Comfort Settings (Normal, Less Aggressive, More Aggressive).
If the unit shows an error code, look it up: Trane General codes
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Control Response Profiles p.9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.