Trane General: No cooling, XR724 not calling
No cooling, XR724 not calling on a Trane general: The XR724 does not start cooling. Check the control settings and timers first, then the equipment.
Applies to: Trane XR724 touchscreen comfort control TCONT724AS42DA (also sold under American Standard)
Common causes of no cooling, xr724 not calling
- System mode not on Cool or Auto, or cool setpoint set too high
- Cooling delta On set too high
- Minimum off time (compressor protection) still counting down
- Problem in the cooling equipment itself
How to fix no cooling, xr724 not calling: step by step
- Check the mode is Cool or Auto and the setpoint is below room temperature.
- Check the cooling delta On. A large value means the room must warm up a lot before it calls.
- Wait out the minimum off time. If the customer finds it too long, change Control Response in Installer Settings > Comfort Settings.
- To split thermostat from equipment, use Menu > Test Mode > Cooling. It energizes Y1 or Y2 with O and G (BK too on a variable speed indoor unit) for 30 minutes.
- If the equipment does not run in Test Mode, the problem is in the wiring or the equipment. Go to the outdoor and indoor unit.
If the unit shows an error code, look it up: Trane General codes
Source: Trane XR724 Comfort Control (TCONT724AS42DA) User Guide and Installer's Guide 18-HD82D1-1E-EN, Troubleshooting p.38 and Test Mode p.8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.