Navien Air Handler: TXV coil: low suction pressure, low superheat
TXV coil: low suction pressure, low superheat on a Navien air handler: What causes low suction with low superheat on a TXV coil.
Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor
Common causes of txv coil: low suction pressure, low superheat
- Low load: low indoor airflow, dirty filter, return air too cold, icing on the indoor coil
- Poor air distribution over the indoor coil
- Wrong indoor/outdoor match on a heat pump (charge balance off between heat and cool)
- Oil trapped in the indoor coil
How to fix txv coil: low suction pressure, low superheat: step by step
- Check the filter, blower and airflow first.
- Check for coil icing and return air temperature.
- Check that the coil and outdoor unit are a proper match.
Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Additional TXV Troubleshooting p.19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.