Navien Air Handler: Leak sensor: wiring check
Leak sensor: wiring check on a Navien air handler: How the NAM leak sensor harness is wired, for checking a no-cool or blower problem after install.
Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor
Common causes of leak sensor: wiring check
- Pigtail on the wrong terminal
- Y-CC wire landed on the contactor common
How to fix leak sensor: wiring check: step by step
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- RED (R) goes to R on the furnace terminal block.
- BLACK (COM) goes to C.
- YELLOW (Y-Tstat) goes to Y or Y1 on the furnace (or the thermostat Y wire).
- WHITE (Y-CC) goes to the Y wire going to the outdoor unit contactor. Never to the contactor common.
- BLUE (G) goes to G on the furnace.
- ORANGE (ALARM) is capped from the factory. It has 24 VAC with no leak and drops to 0 VAC during a leak. Use it only for a BMS or smart thermostat alert.
- Make sure continuous fan speed gives at least the minimum mitigation airflow in Table 4 for the system charge.
Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Refrigerant detection system wiring connections and minimum airflow p.20-22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.