Navien Air Handler: Leak sensor: blower runs and outdoor unit stays off, no leak
Leak sensor: blower runs and outdoor unit stays off, no leak on a Navien air handler: The coil's leak detection system is in mitigation mode with no leak.
Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor
Common causes of leak sensor: blower runs and outdoor unit stays off, no leak
- Real refrigerant leak at the coil
- Sensor failed or at end of life
- Sensor wiring damaged or unplugged
- Sensor plug pointing up and full of water (except Cubic sensors)
How to fix leak sensor: blower runs and outdoor unit stays off, no leak: step by step
- Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
- Check for a leak with a portable detector first.
- In mitigation the indoor blower runs and the 24 V to the outdoor contactor is opened. The blower runs until 5 minutes after the gas level drops below the sensor setpoint.
- Check the sensor harness: plugged in, not damaged, plug pointing down or sideways.
- No leak and the system stays in mitigation: replace the sensor with a Navien-approved one. An adapter harness may come with it.
- Run the verification test after the repair.
Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, 4. Refrigerant Leak Detection System, sequence of operation and sensor replacement p.20-23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.