Reset & cancel: Boiler tips (part 2 of 8)
Short, practical technician tips on reset & cancel for boiler. Check each one against the manual for your exact model before acting.
Acknowledge a fault and view active faults
Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125
On a fault the red fault indicator flashes, '2' flashes on the display and 'Fault' is shown. Acknowledging moves the message to the standard menu and switches off any connected fault message facility. An unresolved fault is shown again the next day and the facility restarts.
- Follow the instructions on the display to acknowledge the fault.
- To see acknowledged faults, select 'Fault' in the standard menu; the current faults are listed.
- If the fault is not remedied, expect it to reappear the next day.
Acknowledge a fault display
Viessmann · Vitotronic 200-H, Model HK1M
Faults show a fault symbol and a flashing fault code. An acknowledged fault comes back on the display if it is still present at 07:00 the next day.
- Scroll through active fault codes with the arrow buttons.
- Press the acknowledge button to clear the displayed fault.
- Fix the cause, because the fault returns if it is not removed by 07:00 the following day.
Acknowledge a fault message
Viessmann · Vitotronic 200-H HK1S/HK3S
Acknowledging confirms the fault has been noted. If the fault is not corrected, it returns at 07:00 the next day and the red fault lamp keeps flashing until the fault is fixed.
- Open the programming unit cover and run fault search.
- Select Yes on the Acknowledge? prompt and confirm.
- Close the cover.
Acknowledge and recall active faults
Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125
A fault shows as a flashing red fault indicator A, '2' flashing on the display and 'Fault' shown. Acknowledging moves the message to the standard menu. If an acknowledged fault is not fixed, the message comes back the next day.
- When a fault shows, follow the on-screen instructions to acknowledge it.
- To view active faults later, select 'Fault' in the standard menu. Current faults are listed.
- Fix the cause using the table for that code, then reset if the table calls for it.
Acknowledge and recall faults on the Vitotronic 100 GC1
Viessmann · Vitotronic 100 GC1 programming unit
A red fault lamp flashes for every fault. Acknowledging hides the message on screen but the lamp keeps flashing, and the message returns the next morning if the fault is still present.
- Scroll through fault codes with the arrow keys.
- Acknowledge the displayed fault with the acknowledge key.
- To view acknowledged faults again, hold the key for about 2 seconds and select the fault with the arrow keys.
- Fix the cause before the following morning to stop the fault returning.
Acknowledge and reset maintenance messages (Vitotronic 100)
Viessmann · Vitotronic 100, GC1
A maintenance message flashes once a set limit is reached. An acknowledged message can be shown again by holding the button for about 3 seconds. If maintenance is done before the message appears, the coding can be reset to clear the limits.
- Scan the maintenance messages with the up or down button.
- Press OK to acknowledge the message. The display clears.
- After maintenance, set coding 24 to 1 and then back to 0 to reset run-hour and period limits.
- If required, reset burner run hours and starts from the scan screen.
- If required, reset max flue gas temperature with the reset combination shown on page 86.
- If coding 24 is not reset, a new message appears on Monday morning.
Acknowledge and reset service message
Viessmann · Vitodens 200-W B2HA 19, 28, 35
Acknowledging the message only clears it for now. An unreset message comes back the following Monday. Reset only after the service is done.
- Press OK to acknowledge the service message.
- After service is complete, press OK and the second key (symbol not legible in the text) together for about 4 seconds.
- Select 'Service functions'.
- Select 'Service reset'.
- Hours run and time interval restart at 0.
Acknowledge and reset the service display
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
The service display appears when the hours or time limits in coding 21 and 23 are reached. An acknowledged message that is not reset will come back on the following Monday. Resetting restarts the hours run and time interval at 0.
- Press OK to acknowledge the service message.
- After the service is done, press OK and the second button together for about 4 seconds.
- Select 'Service functions'.
- Select 'Service reset'.
Acknowledge and reset the service message
Viessmann · Service interval reminder
When a service limit from coding addresses 21 or 23 is reached, the red fault indicator flashes and Service shows on the display. An acknowledged service message that is not reset comes back the following Monday.
- Press OK to acknowledge the service message.
- After the service is done, press OK and the second button together for about 4 sec.
- Select Service functions, then Service reset.
- Hours run and the time interval restart at 0.
Acknowledge fault display
Viessmann · Vitocrossal 200 CI2 boilers
Acknowledging stops any connected central fault facility. If the fault is not fixed it comes back the next day at 07:00 and the central facility restarts.
- Tap the acknowledge button to acknowledge the fault display.
- Fix the fault. Otherwise it will reappear the next day at 07:00.
Acknowledge maintenance display (Vitotronic 300-K)
Viessmann · Vitotronic 300-K, MW1S
The Vitotronic 300-K shows a maintenance message only when it is set as fault manager (coding 79:1) and a maintenance message is active on a connected Vitotronic 100.
- Press the scan button to open maintenance messages.
- Scan the messages with the up or down button.
- Press OK, then confirm the acknowledge prompt with OK.
- Acknowledge the matching message on the Vitotronic 100 (see page 89).
- If coding 24 on the Vitotronic 100 is not reset after maintenance, the message returns on the following Monday morning.
Acknowledge maintenance messages
Viessmann · Vitocrossal 200 CI2 boilers
An acknowledged maintenance message that was not reset comes back the following Monday.
- Open the maintenance message list.
- Acknowledge the maintenance message and confirm.
- Reset the service counter (see reset service tip) so the message does not return.
Acknowledge service message
Viessmann · Vitotronic 200-H, Vitodens 200-W B2HB
A Service message shows when the burner hours or time interval limit is reached. The red fault indicator flashes.
- Press OK to acknowledge the Service message.
- If not reset, the message comes back on the following Monday.
Acknowledging and recalling faults
Viessmann · Vitotronic 100 GC1 programming unit
A fault is acknowledged from the programming unit. The red fault light keeps flashing until the cause is fixed. An acknowledged fault that is not fixed within 24 hours shows up again on the display. Acknowledged faults can be recalled, and a fault from another LON unit shows as its participant number with EE for external fault.
- Press the acknowledge button to clear the displayed fault.
- To recall an acknowledged fault, press and hold the button for about 2 seconds.
- Use the up or down button to select the fault and view it.
Automatic return to standard menu
Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125
Two minutes after the last change, the display goes back to the standard menu. The screen saver starts after a few minutes without setting changes and dims the display.
Basic setting D resets heating circuit values
Viessmann · Vitotronic 200-H HK1M
Basic setting D returns all modified heating circuit values to the factory defaults. Use it only when you want to undo all custom settings.
- Select basic setting D.
- Confirm the reset.
- Re-enter any custom times and temperatures afterwards.
Burner control unit fault and lockout reset
Viessmann · CA3B Dual Fuel 2.5 to 6.0
If the fault lamp on the control unit is lit and the display on the burner control unit is blinking, reset the burner control unit with its reset button R. If the fault returns, the supply side of the combination gas valve may be blocked from gas pipe work. Air in the gas line can also cause a fault on first start-up.
- Press reset button R on the burner control unit.
- If the fault continues, check for a blocked supply side of the combination gas valve after gas pipe work.
- On first start-up with a fault from insufficient gas, ventilate the gas line again.
- Reset the burner control unit again.
- Allow for the 3 minute delay before the burner starts.
Burner fault on first start-up (air in gas line)
Viessmann · Vitocrossal 300 CU3A initial start-up
Air in the gas supply pipe, especially with LPG, can cause a burner fault on initial start-up. Ignition is direct spark.
- Wait about 5 seconds after the fault.
- Press the "R" button to reset the burner.
- The ignition sequence repeats automatically.
Calling up an acknowledged fault message
Viessmann · Vitotronic 100, GC1 boiler controls
An acknowledged fault stays retrievable. The fault message returns the next day if the fault is not fixed, and the red fault lamp keeps flashing until the fault is corrected.
- Press the fault button and hold for about 2 seconds; the fault code is displayed.
- Press the button(s) to view each fault code if several faults occurred together.
- Press the confirm button; the display returns to the boiler temperature.
Cancel energy saving mode
Viessmann · Vitotronic 300 Model GW2
Energy saving mode ends automatically when the preset program next switches to reduced room temperature. To cancel immediately, use the steps below.
- Press the heating circuit selector button.
- Press the energy saving button again; the button goes out.
Cancel or delete a holiday program
Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C
Deletes the holiday program by setting the return date equal to the departure date.
- From the home screen, open Menu, then Heating.
- Select the heating circuit.
- Open Holiday program.
- Set the return date to the same date as the departure date.
- Tap OK to confirm.
Cancel or delete the holiday program
Viessmann · Vitocrossal 300 CU3A
Use the extended menu path for 'Holiday program' under Heating to cancel or delete an active holiday program. The manual text is cut off after step 3, so the final step is not shown on these pages.
- Open the extended menu.
- Select 'Heating'.
- Select 'Holiday program'.
Cancel or erase the holiday program
Viessmann · Vitotronic 200-H holiday program
Ends the holiday program before the return date or clears it during setup.
- Press j again.
- Confirm 'Erase? Yes'.
Cancel party mode
Viessmann · Vitotronic 300 Model GW2
Party mode ends automatically the next time the preset heating program switches to normal room temperature. To stop it immediately, use the button combination below.
- Press the heating circuit selector button.
- Press the party mode button again; the button goes out.
Cancel relay test
Viessmann · Burner test
The relay test ends on its own after 30 minutes if not cancelled.
- Switch the boiler OFF, then back ON to cancel the relay test.
Cancelling a heating circuit assignment
Viessmann · Vitotrol 200A remote control with Vitotronic control unit
If the heating circuit assignment is removed, the coding address of that circuit must also be cleared at the control unit. Otherwise fault messages bC, bd or bE can appear.
- At the Vitotronic control unit, set coding address A0 for this heating circuit back to 0.
Cancelling a time phase change before saving
Viessmann · Time program editing, Vitotronic 300-K
Use the cancel control to stop a time phase adjustment that has not been confirmed.
- Tap the cancel control in the time phase setting to cancel the adjustment or change in progress.
- Use the footer back button to go up one menu level if needed.
Cancelling Economy mode
Viessmann · Central heating heating circuits
Economy mode lowers the room temperature during standard heating mode. It cancels automatically when the time program switches to reduced heating, or when set to OFF. The displayed room temperature setting does not change.
- Open the extended menu, select Heating, select the circuit, then Economy mode.
- Set Economy mode to OFF to cancel it.
Cancelling party mode
Viessmann · HK1S and HK3S
Party mode ends automatically at the next scheduled switch to normal-temperature heating.
- To cancel immediately, press the party button again; the light goes off.
Cancelling the holiday program
Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
The holiday program is cancelled by setting the return date equal to the departure date.
- Go to Menu > Heating > required heating circuit > Holiday program.
- Set Return date to the same date as Departure date.
- Press OK to confirm.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.