Other: Mini-Split tips (part 2 of 8)
Short, practical technician tips on other for mini-split. Check each one against the manual for your exact model before acting.
Discharge electrolytic capacitors before troubleshooting
Carrier · D5FSOAH outdoor PCB
Capacitors keep charge after power is off. Discharge them before touching the board. The discharge resistor value is partly garbled in the source, so confirm it against the unit label.
- Turn off all power and lock out the supply.
- Connect a discharge resistor or a soldering iron plug across the + and - terminals of the electrolytic capacitor (see Fig. 33 and 34 on the outdoor PCB).
- Confirm the capacitor is discharged before troubleshooting.
Discharge the inverter capacitors before service
Carrier · DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)
The big electrolytic capacitors on the outdoor board stay charged after power-off.
- Turn power off and lock out.
- Put a resistor of about 100 ohm 40 W (or a soldering iron plug) across the + and - capacitor terminals before touching the board.
Display and LED indicators
Carrier · All 9K~48K units
All cassette sizes have an LED display that shows operation status and error codes. Indicators include Operation, Timer, Alarm, PRE-DEF (preheating/defrost) and a wireless control indicator on some models.
- Read the LED display for the error code.
- Check the PRE-DEF indicator to see if the unit is in preheating or defrost.
Display code CP (remote switch off)
Carrier · D5FSOAH06XAK, D5FSOAH12XAK, D5FSOAH18XAK
With the remote ON-OFF input open, the system is off and the display shows CP.
- Close the remote ON-OFF contact to restart the system.
Display panel and remote LCD symbols
Carrier · Indoor display panel and wireless remote LCD
The indoor display shows temperature and error codes. Symbols show defrost, timer, SWING or SILENCE, Active Clean, 46°F/8°C heating, and ECO on the unit. The remote LCD shows mode, timers, fan speed, humidity, ECO, GEAR, LOCK, low battery and feature icons.
- Read the indoor display for set temperature, error codes and feature symbols.
- Read the remote LCD for mode, timer, fan speed and feature status.
- If the remote low-battery icon flashes, replace the batteries.
Display panel indicators
Carrier · Indoor unit display panel, D5FSFAH
The display panel shows temperature and error codes. Symbols show defrost on heating units, timer on/off with swing or silence for 3 seconds, Active Clean on, 46°F/8°C heating feature on, and ECO function on.
Downsize D5FSOAH12XAK from 12K to 9K
Carrier · D5FSOAH12XAK
The D5FSOAH12XAK is dual capacity and ships at 12K. ENC1 on the main board sets it to 9K.
- Disconnect power.
- Open the electronic control box.
- Set ENC1 to 2.
- Close the electronic control box.
- Reconnect power. The unit now runs as 9K.
Drainage plug use
Carrier · Indoor unit drain pan
The drainage plug at the bottom of the unit body drains the drain pan when the unit malfunctions. It must be fully plugged during normal operation to prevent leaks.
- Use it only to remove accumulated water after the unit has been switched off.
- After draining, put the test cap back in its original position.
- Confirm the plug is sealed before normal operation.
DRYING mode low room temperature protection
Carrier · D5FSFAH 9K to 16K
In DRYING mode the compressor stops when room temperature is too low, and it does not restart until the room warms up.
- Compressor stops when room temperature drops below 50 F (10 C).
- Compressor restarts only after room temperature exceeds 53.6 F (12 C).
Drying mode operation and low room temperature protection
Carrier · D5FCFAH
Indoor fan is fixed at BREEZE and cannot be changed. Louver angle matches cooling. If room temperature is below 50°F (10°C) the compressor stops and does not restart until the room exceeds 53.6°F (12°C).
- If the compressor will not restart in drying mode, check room temperature against 53.6°F (12°C).
Electrical isolation and lockout before service
Carrier · All D5FCFAH indoor and outdoor units
Electrical shock hazard. Power must be isolated before any installation or repair work.
- Switch off the main electrical disconnect before installing, modifying or servicing the system.
- Check for more than one disconnect and switch off all of them.
- Lock out and tag each disconnect with a warning label.
- Use a dedicated circuit and do not share the outlet with other appliances.
- Confirm the fixed wiring has an all-pole disconnect with at least 3 mm contact gap and a 30 mA RCD where required.
Electrical safety checks before work on sealed or live electrical parts
Carrier · D5FSOAH indoor and outdoor units
Disconnect power before opening covers. If supply must stay on during service, leak detection must be running at the most critical point.
- Switch off the main electrical disconnect before installing, modifying or servicing. Lock out and tag it. There may be more than one disconnect.
- Discharge capacitors in a safe way that avoids sparks.
- Check that no live parts or wiring are exposed while charging, recovering or purging.
- Check that earth bonding is continuous.
- Check that cables are not worn, corroded, pinched or under vibration stress.
- Replace sealed electrical components and intrinsically safe components only with parts specified by the manufacturer.
- Make sure seals and glands are intact so flammable atmospheres cannot enter the enclosure.
Electrical supply and disconnect
Carrier · Power supply and wiring for 18K to 60K units
Supply and disconnect requirements shown on the wiring pages.
- Connect the indoor and outdoor units to 208/230V, 60 Hz as shown in the connection diagram.
- Use a disconnect in the fixed wiring per NEC, CSA and local codes.
- Provide a separate circuit breaker for the electric heater unit power wires as shown in the wiring overview.
- Use the wiring diagram that matches the unit size.
Electrical supply and disconnect requirements
Carrier · Indoor and outdoor units, fixed wiring
Installation work requires power to be off and locked out. The fixed wiring needs an all-pole disconnect and an RCD.
- Switch the main disconnect OFF before installing or servicing. Lock out and tag it, because there may be more than one disconnect.
- Use an all-pole disconnect with at least 3 mm contact clearance in every pole, as NEC, CSA and local codes require.
- Fit a residual current device (RCD) rated at 30 mA or less for leakage that may exceed 10 mA.
- Do not share the outlet with other appliances.
- Only use the specified wire, and clamp all cables tight. Keep the control board cover able to close properly.
Electronic control box subassembly removal
Carrier · D5FSOAH, sizes 06K to 18K
Electrical parts are removed after the panel is off. Only the final removal steps are on these pages.
- Remove the panel first.
- Remove the 4 screws holding the electronic control box subassembly.
- Lift out the electronic control box subassembly.
Evaporator removal
Carrier · D5FSOAH, sizes 06K to 18K
Remove the panel, water collector and water pump first. The coil temperature sensor T2 is pulled out during this job.
- Remove the panel, water collector and water pump.
- Remove the 2 screws of the pipe clamp board.
- Remove the 2 screws on the left side of the evaporator bracket.
- Remove the 2 screws on the right side of the evaporator.
- Cut the zip tie, pull out the coil temperature sensor (T2) and remove 1 ground screw.
- Remove the evaporator.
Fan motor and fan removal
Carrier · D5FSOAH, sizes 06K to 18K
Remove the panel, electrical parts, water collector, water pump and evaporator first.
- Remove the panel, electrical parts, water collector, water pump and evaporator.
- Remove the 2 screws of the fan motor base.
- Pull out the fan motor and fan assembly.
- Remove the screw and take off the fan motor.
Flammable refrigerant and leak sensor handling
Carrier · Units with a refrigerant leak sensor
Rules for working on systems with an R-32 style flammable refrigerant and a leak sensor.
- Only trained service personnel may repair this unit. Do not puncture refrigerant tubing.
- Test joints with a detector rated for 1/8 oz (5 g) per year or better.
- Keep ventilation openings clear of obstruction.
- Replace the refrigerant sensor only with the manufacturer-specified sensor. Sensors cannot be repaired.
- Sensor service life is 15 years.
Flammable refrigerant: safe work practices
Carrier · All D5FSOAH indoor and outdoor units
The unit uses a flammable refrigerant. Only trained technicians holding a current refrigerant-handling certificate may open the refrigerant circuit. Do not pierce or burn refrigerant tubing, and do not use ignition sources near the work area. Refrigerant may have no odour, so detection equipment is needed.
- Check the area with a refrigerant detector before and during work.
- Use only leak detection that is non-sparking and suitable for flammable refrigerant. Never use a halide torch or a naked flame.
- Remove or extinguish all naked flames and ignition sources before opening the system.
- Keep a dry powder or CO2 extinguisher next to the charging area when hot work is planned.
- Ventilate the area before breaking into the system or doing hot work, and keep ventilation running during the job.
- Do not use means to speed up defrosting or cleaning other than those the manufacturer recommends.
- Keep the unit stored in a room without continuously operating ignition sources.
Fresh-air fan output CN8
Carrier · Indoor unit controls
CN8 is line voltage (208 or 230 V) while the indoor blower runs. It is off during forced cooling or capacity test mode.
- Use CN8 to power a relay for an outdoor air fan or other peripheral.
- Do not expect CN8 to be live during forced cooling or capacity testing.
Fuse replacement rule
Carrier · Unit power supply
Replace a blown fuse only with one of identical rating. A higher or lower amperage fuse can damage the circuit or cause an electrical fire.
- Disconnect power before work.
- Fit a fuse with the same rating as the one removed.
Handle pipe connectors A and B safely
Carrier · D5FSHA sizes 6K to 36K
Connectors A and B are pressurised and can release on removal.
- Wear work gloves and goggles.
- Do not point connectors A and B toward people.
- Hold the cross-shape part of connector B with a wrench or channel locks for about 5 to 10 seconds until the red point of connector A fully retracts.
- Remove connectors A and B, then make the refrigerant connection.
Heating at 46°F (8°C) mode
Carrier · D5FCFAH
When the compressor runs, the indoor fan runs without anti-cold air. When the compressor is off, the indoor fan is off.
Indoor coil protections and heating setback
Carrier · Indoor units, sizes 06 to 36
Indoor units include freeze-up protection and cold blow protection on heat pumps. High temperature protection in heating mode detects excessive discharge temperature. A 46°F heating mode (heating setback) is standard. Auto restart returns the unit to its prior operating conditions after a power failure.
Indoor unit dimensions
Carrier · D5FSOAH indoor unit, sizes 6K to 18K
Figure 1 gives the indoor unit footprint and ceiling hole sizes. Legible values are 16.65 in (423 mm), 13.19 in (335 mm), 43.5 in (1105 mm), 9.84 in (250 mm), 53.54 in (1360 mm), 18.4 in (475 mm), 8.07 in (205 mm) and 7.87 in (200 mm). The figure labels are partly garbled, so confirm each dimension against the drawing before cutting the ceiling hole.
Indoor unit supplied parts and recommended tools
Carrier · D5FSHA indoor unit installation
Parts list (numbering from the figure): wall mounting plate, connection cable (buy separately), remote controller, drain pipe (buy separately), refrigerant piping (buy separately), louver, remote controller holder, air filter (pulls up), front panel, outdoor unit power cable, circuit breaker. Recommended tools: gloves, screwdriver and wrench, goggles and masks, vinyl tape, hammer drill, core drill.
- Confirm all parts listed for the unit are on hand before starting.
- Buy the connection cable, drain pipe and refrigerant piping separately.
- Have a hammer drill and core drill ready for the wall hole.
Indoor wiring diagram legend
Carrier · 9K~18K wiring diagram
Legend terms used on the indoor unit wiring diagram.
- Y/G: yellow-green conductor (ground).
- PUMP: condensate pump.
- TO CCM Comm. Bus: central controller communication bus.
- T1: indoor room temperature sensor.
- T2: indoor heat exchanger coil temperature sensor.
Indoor-to-outdoor wiring rules
Carrier · D5FSCAH / D5FLCAH
Rules for connecting the indoor and outdoor units and field wiring.
- Do not use thermostat wire between indoor and outdoor units.
- Wire indoor-to-outdoor connections exactly as shown. Polarity matters, and wrong polarity causes a fault code.
- Use the wire size specified in the product data for each indoor unit.
- Do not connect power wire to a signal terminal.
- Do not splice control wires.
- Keep wiring with different voltages in separate conduits.
- Avoid metal conduit to reduce noise and EMI.
- Make sure each wire lands on the matching terminal on the indoor and outdoor units.
- Ground the equipment and install a current leakage protection switch as required by local rules.
Inquiry codes 12 and 13 - conflicting labels
Carrier · Inquiry codes 12 and 13
Code 12 is labelled Pr (indoor fan speed) in the table, but its description covers the heating frequency lower limit. Code 13 is labelled Lr (EEV opening), but its description covers the T4 cooling-only maximum operating frequency. Confirm the function on the unit before changing either value.
- Verify the displayed function before changing code 12 or 13.
- Do not change these values without confirming the correct function.
Installation clearance near auxiliary heater
Carrier · Units with auxiliary electric heater
Units with an auxiliary electric heater need clearance from combustible materials.
- Do not install the unit within 3 feet (1 meter) of any combustible material.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.