Viessmann Mini-Split: Wired remote control installation
Wired remote control installation on a Viessmann mini-split: The connection point depends on the wired controller model and the indoor unit size.
Applies to: Wired controllers on sizes 12 to 58
How to fix wired remote control installation: step by step
- For KSACN0101AAA (timer), connect to the 4-pin connector on the display board, on all sizes 12 to 58.
- For KSACN0401AAA (7-day programmable) on size 12, cut the J1 jumper on the main control board, then connect to the 4-pin connector on the net module attached to CN20.
- For KSACN0501AAA (7-day programmable) on sizes 18 to 58, connect to the 4-pin connector on CN40 of the main control board.
- Follow the controller installation manual for setup.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: DLFSFA and DLFLFA installation instructions, p. 13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.