Viessmann Mini-Split: Power and communication wiring, sizes 36 to 58
Power and communication wiring, sizes 36 to 58 on a Viessmann mini-split: Power runs from the outdoor unit to the indoor unit on three conductors: two high-voltage AC and one ground, factory recommended 14/2 stranded with ground. Communication needs its own separate shielded stranded copper conductor rated 600 V, double insulated.
Applies to: DLFLFAH36XAK, DLFLFAH48XAK, DLFLFAH58XAK
How to fix power and communication wiring, sizes 36 to 58: step by step
- Size all wires per NEC or CEC and local code, using the electrical data MCA and MOCP values.
- Run 14/2 stranded power wire with ground from the outdoor unit to the indoor unit.
- Run a separate shielded 16 GA stranded control wire for communication, rated 600 V with double insulation.
- Tighten every connection and keep wires away from refrigerant tubing, the compressor and moving parts.
- Make sure a disconnect is within sight of and readily accessible from the unit.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: Vitocal IND-F DLFSFA/DLFLFA installation manual, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.