Viessmann Mini-Split: Power and communication wiring, sizes 12 to 24
Power and communication wiring, sizes 12 to 24 on a Viessmann mini-split: Power is fed to the outdoor unit and runs to the indoor unit on a field-supplied 14/3 cable. Two conductors are high-voltage AC, one is communication, and one is ground. Use the shielded 14/2 option only in high EMF areas where communication problems occur.
Applies to: DLFSFAH12XAK, DLFSFAH18XAK, DLFSFAH24XAK
How to fix power and communication wiring, sizes 12 to 24: step by step
- Size all wires per NEC or CEC and local code, using the electrical data MCA and MOCP values.
- Run a 14/3 power and communication cable from the outdoor unit to the indoor unit.
- If communication faults occur in a high EMF area, replace L2 and S with 14/2 stranded shielded wire.
- Land the shield on ground at the outdoor unit only.
- Tighten every connection and keep wires away from refrigerant tubing, the compressor and moving parts.
- Make sure a disconnect is within sight of and readily accessible from the unit.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: Vitocal IND-F DLFSFA/DLFLFA installation manual, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.