Viessmann Mini-Split: Make the refrigerant flare connections
Make the refrigerant flare connections on a Viessmann mini-split: Clean square cuts and correct torque are needed for leak-free flare joints.
Applies to: DLFSHC indoor units
How to fix make the refrigerant flare connections: step by step
- Cut the pipe square at 90 degrees with a pipe cutter.
- Remove the service connection if the unit has one.
- Remove all burrs from the cut edge, and make sure none fall inside the tube.
- Remove the flare nuts from the indoor and outdoor unit connections.
- Install the correct size flare nut onto the tubing and make the flare. Check the flare nut spacing in Table 6.
- Apply a small amount of refrigerant oil to the flare.
- Align the pipe centre with the connection or service valve.
- Connect both the liquid and gas lines to the indoor unit.
- Tighten the flare nut with a torque wrench to the value in Table 7.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
DLFSHCH06XAKDLFSHCH09XAKDLFSHCH12XAJDLFSHCH12XAKDLFSHCH18XAKDLFSHCH24XAKDLFSHCH30XAKDLFSHCH36XAK
Source: DLFSHC installation instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.