Viessmann Mini-Split: Indoor fan speed too low
Indoor fan speed too low on a Viessmann mini-split: Indoor fan speed protection. Fan speed can drop below the minimum for a set time.
Applies to: Indoor fan motor and control
Common causes of indoor fan speed too low
- Indoor fan speed remains below 300 RPM
How to fix indoor fan speed too low: step by step
- Expect the indoor fan to shut off after 50 seconds at low speed and restart 30 seconds later.
- If the protection trips three times while the fan keeps restarting, the unit stops and the LED shows the failure.
- Check the indoor fan motor, its wiring and the control board, then restart the unit.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Source: DLFSOAH Service Manual, p. 7-8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.