Viessmann Mini-Split: Evacuate and charge system with vacuum pump
Evacuate and charge system with vacuum pump on a Viessmann mini-split: Evacuate all circuits at once through the low side master service valve charge port. Break vacuum with dry nitrogen only. Factory charge in the outdoor unit covers line length up to 25 ft (8 m). Note: all units except the 18,000 BTU model have a master suction and liquid line service valve.
Applies to: System evacuation and charging, all DLFSHC sizes
How to fix evacuate and charge system with vacuum pump: step by step
- Tighten the flare nuts (A, B, C, D, E) fully.
- Fully open all circuit service valves.
- Connect the manifold gauge charge hose to the charge port of the low side master service valve.
- Connect the other charge hose to the vacuum pump.
- Fully open the low side of the manifold gauge.
- Start the vacuum pump and evacuate using the triple evacuation method.
- When evacuation is complete, fully close the low side of the gauge manifold and stop the pump.
- Disconnect the charge hose from the low side service valve charge connection.
- Tighten the service valve caps securely.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
DLFSHCH06XAKDLFSHCH09XAKDLFSHCH12XAJDLFSHCH12XAKDLFSHCH18XAKDLFSHCH24XAKDLFSHCH30XAKDLFSHCH36XAK
Source: DLFSHC service manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.