Viessmann Mini-Split: Drill the wall hole for connecting piping
Drill the wall hole for connecting piping on a Viessmann mini-split: The wall hole must slope down to the outside so condensate drains properly.
Applies to: DLFSHC indoor units
How to fix drill the wall hole for connecting piping: step by step
- Find the wall hole position from the mounting plate dimensions and the figures for the unit size.
- Drill with a 2.5 in (65 mm) core drill, or a 3.54 in (90 mm) core drill if the gas line is 5/8 in (16 mm) or larger.
- Drill slightly downward so the outside end is about 0.2-0.275 in (5-7 mm) lower than the inside end.
- Fit the protective wall cuff in the hole.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
DLFSHCH06XAKDLFSHCH09XAKDLFSHCH12XAJDLFSHCH12XAKDLFSHCH18XAKDLFSHCH24XAKDLFSHCH30XAKDLFSHCH36XAK
Source: DLFSHC installation instructions, p. 10-11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.