Updated · by Aurora Star Tech Inc.

DC fan motor test (indoor and outdoor) on a Viessmann mini-split: Checks whether the fault is in the fan motor or in the PCB.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DLFSOAH 09XAK / 18XAK

How to fix dc fan motor test (indoor and outdoor): step by step

  1. Indoor: power on, put the unit in STANDBY, and measure voltage at the fan motor connector pin1-pin3 and pin4-pin3. Compare with the signal table.
  2. Indoor: if the voltage is out of range, the PCB has failed; replace it.
  3. Outdoor: shut off power, release the UVW connector, and measure resistance U-V, U-W and V-W.
  4. Outdoor: if the three resistances are not equal, replace the fan motor.
  5. Outdoor: if the three resistances are equal, replace the outdoor PCB.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Mini-Split codes

Source: DLFSOAH Service Manual, p. 19-20. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.