Viessmann Heat Pump: Power and communication wiring between indoor and outdoor units
Power and communication wiring between indoor and outdoor units on a Viessmann heat pump: Use stranded copper wire rated 600 V, sized per NEC/CEC and local code using the MCA and MOCP values in the electrical data. Power and communication run together from the outdoor unit to the indoor unit. The main line voltage goes on terminals 1 and 2, the communication wire on terminal 3, and green ground on the ground terminal. Keep every connection tight. No wire may touch refrigerant tubing, the compressor or moving parts. If there is high EMF interference, a 14/2 stranded shielded wire can replace the 2 and 3 conductors, with the shield grounded at the outdoor unit only.
Applies to: DLFSHCH indoor and outdoor unit wiring
How to fix power and communication wiring between indoor and outdoor units: step by step
- Size wires and disconnect per NEC/CEC, local code and the MCA/MOCP values.
- Use stranded copper, 600 V rated wire only.
- Connect L1 to terminal 1, N or L2 to terminal 2, communication to terminal 3, green to ground.
- Check the 115 V or 208/230 V connection diagram before landing wires.
- Tighten all connections and keep wires clear of tubing, compressor and moving parts.
- If EMF interference is present, use shielded 14/2 for conductors 2 and 3 and ground the shield at the outdoor unit only.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
More commissioning tips for heat pump
Source: Vitocal IND-H DLFSHC service manual, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.