Viessmann Heat Pump: Compressor winding resistance check

Updated · by Aurora Star Tech Inc.

Compressor winding resistance check on a Viessmann heat pump: Checks the compressor windings for balance when a compressor or IPM fault is suspected.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Compressor, PC00 fault

How to fix compressor winding resistance check: step by step

  1. Disconnect the compressor.
  2. Measure resistance between U-V, V-W and U-W.
  3. All three values should be equal.
  4. If they are not equal, the compressor is faulty and must be replaced.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Source: DLFSHC Service Manual, p. 29. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.