Viessmann Boiler: Wiring the Vitodens 100-W WB1A/WB1B boiler to the Versatronik 10.WB1
Wiring the Vitodens 100-W WB1A/WB1B boiler to the Versatronik 10.WB1 on a Viessmann boiler: Interconnect the boiler pump module with the Versatronik for the low voltage DHW and room thermostat signals and for the 120VAC pump supply and pump signal. Power is applied only after all connections are checked.
Applies to: Vitodens 100-W WB1A and WB1B with Versatronik 10.WB1
How to fix wiring the vitodens 100-w wb1a/wb1b boiler to the versatronik 10.wb1: step by step
- Disconnect the boiler and the Versatronik from 120VAC before starting any work.
- Wire X4.1 and X4.2 from the Vitodens pump module to the WB1 DHW terminals (X7.1 and X7.2) on the Versatronik.
- Wire X4.3 and X4.4 from the Vitodens pump module to the WB1 RT terminals (X8.3 and X8.4) on the Versatronik.
- Wire the N and L boiler pump output from the Vitodens pump module to the WB1 pump N and L input on the Versatronik PCB.
- Connect the room thermostat as a potential-free contact only, with no voltage applied. Do not use it with the Versatronik Como OT.
- Connect the DHW call as a potential-free contact from a set-point control or DHW tank aquastat, with no voltage applied.
- Connect the DHW pump (120VAC, 3 FLA output) and the space heating pump (120VAC, 3 FLA output).
- Check all connections before applying 120VAC to the Versatronik.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 10.WB1 installation manual, p. 10-11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.