Viessmann Boiler: Wiring the Versatronik 10.WB1 to a space heating zone controller
Wiring the Versatronik 10.WB1 to a space heating zone controller on a Viessmann boiler: The Versatronik space heating pump output is used as a control signal to the field zone controller. Zone pumps or valves only run on a zone call while the Versatronik output is on. This setup is for an outdoor reset application with no room thermostat.
Applies to: Boiler with Versatronik Como OT and outdoor reset, no room thermostat
Common causes of wiring the versatronik 10.wb1 to a space heating zone controller
- No signal output from the Versatronik means the zone controller will not start any zone on a thermostat call
How to fix wiring the versatronik 10.wb1 to a space heating zone controller: step by step
- Disconnect power from the Versatronik 10.WB1 and the zone control.
- Remove the ZC/ZR jumper from the zone controller.
- Connect the L output from the Versatronik 10.WB1 space heating pump to ZC on the zone controller.
- Power both devices and test operation.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 10.WB1 installation manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.