Viessmann Boiler: Vitotronic 200 cascade coding entry
Vitotronic 200 cascade coding entry on a Viessmann boiler: The Vitotronic 200 is coded from the boiler control. The boiler must already be in cascade mode before coding.
Applies to: Vitotronic 200 multi boiler coding
How to fix vitotronic 200 cascade coding entry: step by step
- Confirm the boiler is in cascade mode (see boiler service instructions).
- Press OK and the service button for about 4 seconds.
- Scroll to service and select with OK.
- Scroll to service functions and select with OK.
- Scroll to multi-boiler system and select with OK.
- When finished, press the exit button to leave.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.