Viessmann Boiler: Update participant list (Vitocontrol-S cascade)
Update participant list (Vitocontrol-S cascade) on a Viessmann boiler: Run this after all communication connections are made, with the Vitocontrol-S coded as error manager (default). Each gateway needs a unique LON participant number set on its rotary dial.
Applies to: Vitocontrol-S cascade control with Versatronik 505 gateways
How to fix update participant list (vitocontrol-s cascade): step by step
- Confirm the Vitocontrol-S is coded as error manager (see Vitocontrol-S manual, address 79:01).
- Check that no two gateways share a rotary dial LON participant number.
- Press OK and Menu together to open the Service screen, then press OK.
- Arrow down to Service Functions and press OK.
- Make sure Subscriber Check is highlighted, then press OK.
- Arrow down to Delete List? and press OK.
- Wait for devices to report back, then run the subscriber check again.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 505 and 505D BACnet IP manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.