Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Update LON participant list for Vitocontrol-S cascade control

Updated · by Aurora Star Tech Inc.

Update LON participant list for Vitocontrol-S cascade control on a Viessmann boiler: Run this after all communication connections are made. Vitocontrol-S must be the error manager (default), and every gateway needs a unique LON participant number.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocontrol-S cascade control with Versatronik 505 gateways

How to fix update lon participant list for vitocontrol-s cascade control: step by step

  1. Confirm Vitocontrol-S is coded as error manager (default). Refer to the Vitocontrol-S manual, address 79:01.
  2. Set the rotary dial LON participant number on each Versatronik 505 gateway and make sure no two numbers match.
  3. Press OK and the Menu button together to open the Service menu, then press OK.
  4. Arrow down to Service Functions and press OK.
  5. On the Service Functions screen, make sure Subscriber Check is highlighted. Arrow up or down to highlight it if needed, then press OK.
  6. Arrow down to Delete List? and press OK.
  7. Wait for the participant list to update with the boiler controls and other Versatronik LON devices.
  8. If the screen shows No Subscriber, wait some time and run Subscriber Check again. Devices can take time to report back.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More commissioning tips for boiler

Source: Versatronik 505 NR2/BACIP manual, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair