Viessmann Boiler: System layout: no low loss header
System layout: no low loss header on a Viessmann boiler: There is no low loss header and no dedicated boiler pump. The Vitodens pump module output signal goes to the Versatronik, which gives DHW priority over the space heating pump.
Applies to: Systems without low loss header
How to fix system layout: no low loss header: step by step
- Connect the space heating pump to the Versatronik 10.WB1.
- Connect the DHW pump to the Versatronik 10.WB1.
- Connect the DHW demand from an aquastat or set-point control to the Versatronik 10.WB1.
- Connect the pump output signal from the Vitodens pump module to the Versatronik 10.WB1.
- Check that DHW priority over the space heating pump is set up as intended.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 10.WB1 installation manual, p. 13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.