Viessmann Boiler: Supply and return temperature sensor installation
Supply and return temperature sensor installation on a Viessmann boiler: The supply sensor goes in an immersion well. The return sensor is optional and only lets the user see the temperature difference; it has no control logic.
Applies to: Versatronik 300 Cascade Control, supply sensor S2, return sensor S3
How to fix supply and return temperature sensor installation: step by step
- Push the immersion sensor fully into the temperature well and secure it with the well clip.
- If there is no well, strap the sensor tight to the pipe with conductive paste and a metal strap. Do not use wire ties.
- Insulate over the sensor after it is secured.
- Wire the supply sensor to the S2 terminals inside the control.
- If fitting the optional return sensor, install it in a well or on the pipe and wire it to the S3 input.
- Keep the wiring away from high voltage and shield it as required.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.