Viessmann Boiler: Showing Viessmann fault codes in hex or as text on the BMS
Showing Viessmann fault codes in hex or as text on the BMS on a Viessmann boiler: The gateway sends fault codes as a decimal SNVT_count value, but Viessmann controls show them in hexadecimal. Decode them in the BMS software, for example in Niagara AX.
Applies to: Versatronik 501 / 501D LON gateway fault display
How to fix showing viessmann fault codes in hex or as text on the bms: step by step
- Use a mask object (Numeric Bit And in KitControl Util) to show the code in hexadecimal.
- To show the fault text, use a Numeric To Enum conversion (KitControl Conversion) and enter the enum range for all Viessmann error codes.
- Point a Bound Label on the px webpage at the matching slot values to display the text.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 501 LON communication manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.