Viessmann Boiler: Set BACnet device ID and IP before joining the network
Set BACnet device ID and IP before joining the network on a Viessmann boiler: Applies only to unit 704092 with BACnet/IP. The BACnet Device ID must be unique across the entire BACnet internetwork. Changes do not take effect until Activate Configuration is confirmed.
Applies to: Versatronik 300 unit 704092 with BACnet/IP
How to fix set bacnet device id and ip before joining the network: step by step
- Connect the Ethernet cable to the BACnet port closest to the middle of the control.
- Connect the computer directly to the BACnet port with no other devices attached.
- Set the computer to DHCP, or set its IP to 192.168.88.90 with mask 255.255.255.0.
- Cycle power on the Versatronik 300.
- Browse to http://192.168.88.89/admin and log in.
- Change the default password in the Change Password screen if required.
- Set the BACnet device settings, pressing SAVE on each screen.
- Confirm Activate Configuration and save to reboot.
- Write down any changes made, since they are required later.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
More commissioning tips for boiler
Source: Versatronik 300 Cascade Control V1.4 manual, p. 19-21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.