Viessmann Boiler: Pumps do not switch off

Updated · by Aurora Star Tech Inc.

Pumps do not switch off on a Viessmann boiler: Heating pumps keep running when they should stop.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Versatronik 200 heating circuits

Common causes of pumps do not switch off

  • Wrong pump switching type or operating mode.
  • Outside temperature, room temperature or heating limit settings keep the pump on.

How to fix pumps do not switch off: step by step

  1. Check the pump switching type in the Expert level for the heating circuit.
  2. Check the operating mode is Standard F (test B).
  3. Check the time and heating program (heating time).
  4. Default mode: check outside temperature is above the room set temperature.
  5. Temperature limits: check outside temperature is above the valid heating limit.
  6. Room control: check room temperature is above the temperature setting plus 1 K.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Versatronik 200 installation and operating manual, p. 166-167. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.