Viessmann Boiler: Pumps do not switch off
Pumps do not switch off on a Viessmann boiler: Heating pumps keep running when they should stop.
Applies to: Versatronik 200 heating circuits
Common causes of pumps do not switch off
- Wrong pump switching type or operating mode.
- Outside temperature, room temperature or heating limit settings keep the pump on.
How to fix pumps do not switch off: step by step
- Check the pump switching type in the Expert level for the heating circuit.
- Check the operating mode is Standard F (test B).
- Check the time and heating program (heating time).
- Default mode: check outside temperature is above the room set temperature.
- Temperature limits: check outside temperature is above the valid heating limit.
- Room control: check room temperature is above the temperature setting plus 1 K.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 200 installation and operating manual, p. 166-167. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.