Viessmann Boiler: Participant check (LON communication test)
Participant check (LON communication test) on a Viessmann boiler: Confirms communication between the boiler controls and the Vitocontrol-S system control, one subscriber at a time.
Applies to: Versatronik 505 gateway on Viessmann boiler controls and Vitocontrol-S cascade
How to fix participant check (lon communication test): step by step
- Confirm the Vitocontrol-S is error manager and each gateway has a unique rotary dial participant number.
- Press OK and Menu together for about 2 seconds to open the Service screen.
- Arrow down to Service Functions.
- Select Subscriber Check if not already highlighted, then press OK.
- Arrow up or down to pick a subscriber and press OK. The screen shows whether the check is active and reports OK or not.
- If it passes, pick another subscriber and repeat.
- Press the return button to exit the subscriber check.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 505 and 505D BACnet IP manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.