Viessmann Boiler: Outside temperature sensor installation
Outside temperature sensor installation on a Viessmann boiler: Mount the outside sensor where it reads true outdoor air. Keep it away from windows, doors and vents, and never cover it.
Applies to: Outside temperature sensor on Vitotronic 300-K
How to fix outside temperature sensor installation: step by step
- Mount on a north or north-west wall, 6.6 to 8.2 ft (2 to 2.5 m) above ground level.
- In multistorey buildings, mount in the upper half of the second floor.
- Do not mount above windows, doors or ventilation outlets.
- Do not mount immediately below balconies or gutters.
- Do not cover the sensor.
- Connect with two-wire communication cable, AWG 18, maximum 120 ft (35 m).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 200 and 300-K installation and service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.