Outside temperature sensor installation on a Viessmann boiler: Mount the outside sensor where it reads true outdoor air. Keep it away from windows, doors and vents, and never cover it.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Outside temperature sensor on Vitotronic 300-K

How to fix outside temperature sensor installation: step by step

  1. Mount on a north or north-west wall, 6.6 to 8.2 ft (2 to 2.5 m) above ground level.
  2. In multistorey buildings, mount in the upper half of the second floor.
  3. Do not mount above windows, doors or ventilation outlets.
  4. Do not mount immediately below balconies or gutters.
  5. Do not cover the sensor.
  6. Connect with two-wire communication cable, AWG 18, maximum 120 ft (35 m).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

MW1SVitotronic 300-K, type MW2B

Source: Vitotronic 200 and 300-K installation and service instructions, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.