Viessmann Boiler: Outdoor temperature sensor installation
Outdoor temperature sensor installation on a Viessmann boiler: Mount the outdoor sensor 2 to 2.5 m (6.5 to 8 ft) above ground on a north or north-west wall. In multi-storey buildings, mount it in the upper half of the second storey. Keep it away from windows, doors, vents, balconies and gutters, and do not paint the housing.
Applies to: Outdoor temperature sensor AF S
How to fix outdoor temperature sensor installation: step by step
- Remove the sensor cover.
- Mount the rear section to the wall with field-supplied hardware.
- Feed the wire into the strain relief at the bottom of the housing.
- Connect the wire to the sensor terminals and tighten.
- Refit the cover.
- Plug the 2-pole plug into socket F9 on the control.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 200 installation manual, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.