Viessmann Boiler: Outdoor sensor fault appears on Vitodens if sensor is missing
Outdoor sensor fault appears on Vitodens if sensor is missing on a Viessmann boiler: An outdoor temperature sensor fault will always show on the boiler if the sensor is not connected. A resistor can be used in place of the sensor to fake a warm outdoor temperature.
Applies to: Vitodens 200 WB2B and B2HA
Common causes of outdoor sensor fault appears on vitodens if sensor is missing
- Outdoor temperature sensor not connected to the boiler control
How to fix outdoor sensor fault appears on vitodens if sensor is missing: step by step
- Connect the outdoor temperature sensor inside the boiler housing.
- If no sensor is used, fit a 10 kOhm resistor (brown-black-orange) in its place.
- Expect this resistor to read about 77F/25C, which is above the 68F/20C threshold.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Versatronik 300 Cascade Control V1.4 manual, p. 16-17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.