Viessmann Boiler: LON wiring, Vitocontrol-S MW2 or Vitotronic 300-K MW2B (Vitodens 200 / WB2B)
LON wiring, Vitocontrol-S MW2 or Vitotronic 300-K MW2B (Vitodens 200 / WB2B) on a Viessmann boiler: Wiring layout for the 120VAC and 24VAC gateway on a Vitocontrol-S MW2 for Vitodens 200 WB2B, or a Vitotronic 300-K MW2B. A communication card is required for the 300-K.
Applies to: Vitocontrol-S MW2, Vitotronic 300-K MW2B, Vitodens 200 WB2B
How to fix lon wiring, vitocontrol-s mw2 or vitotronic 300-k mw2b (vitodens 200 / wb2b): step by step
- Install the LON communication card in the control (required for Vitotronic 300-K MW2B).
- Plug the 3 ft CAT-5 cable into the control's RJ45 socket and the other end into the gateway's internal RJ45 socket.
- Wire the LON 2-wire connection to gateway terminals A and B.
- For 120VAC, use the plug-in power cord. For 24VAC, use a field-supplied 24VAC supply.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 501 and 501D LON gateway manual, p. 12-13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.