Viessmann Boiler: LON participant check
LON participant check on a Viessmann boiler: The participant check tests communication between the fault manager and the devices on the LON system. The control must be the fault manager (code 79:1) and the participant list must be current.
Applies to: Vitotronic 300-K and 200-H on LON
How to fix lon participant check: step by step
- Confirm the control is set as fault manager (code 79:1).
- Confirm each control has its LON participant number set.
- Press OK and the service button together for about 4 seconds.
- Select Service functions, then Participant check.
- Select the participant to test (e.g. participant 12).
- Read the result: OK means passed, Not OK means failed.
- To run a new check, create a new participant list with Delete list?.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitotronic 200-H
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Vitotronic 300-K
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.