Viessmann Boiler: INT boiler disable interlock wiring
INT boiler disable interlock wiring on a Viessmann boiler: The INT input takes a potential-free dry contact. The plant shuts down when the contact is open. Closing the contact allows operation.
Applies to: INT terminals
How to fix int boiler disable interlock wiring: step by step
- Wire the BMS or mechanical control (damper or blower motor) through a field-supplied relay to the INT terminals.
- Use an AC or DC relay coil with the correct control voltage. The contact must close for the boiler plant to run.
- Use low-voltage wiring and keep it away from 120/240 VAC conductors.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.