Viessmann Boiler: Installing a 3-way mixing valve actuator adaptor
Installing a 3-way mixing valve actuator adaptor on a Viessmann boiler: Install a 120V or 24V valve adaptor on the DIN rail inside the connection enclosure, then wire the actuator through it. The actuator runtime is set with coding addresses.
Applies to: 3-way mixing valve actuator (A1, M2, M3)
How to fix installing a 3-way mixing valve actuator adaptor: step by step
- Disconnect power to the control.
- Install the 120V or 24V valve adaptor on the DIN rail in the connection enclosure.
- Insert plug gS into socket gS on the Vitotronic.
- Fasten the cable with a tie.
- Connect the adaptor's black wire to terminal 8, 9 or 10 on the DIN rail.
- Connect the valve actuator wires to the adaptor terminals.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitotronic 200
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Vitotronic 300-K
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 200 and 300-K Installation and Service, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.