Viessmann Boiler: Initial BACnet/IP gateway configuration
Initial BACnet/IP gateway configuration on a Viessmann boiler: Connect a laptop directly to the gateway on an isolated network, then open the configuration pages in a browser.
Applies to: Versatronik 505 NR2/BACIP and 505D NR2/BACIP gateways
How to fix initial bacnet/ip gateway configuration: step by step
- Connect the computer directly to the gateway BACnet interface with no other devices attached.
- Set the computer to automatic IP (DHCP), or set its IP to 192.168.88.90 with subnet mask 255.255.255.0.
- Cycle the gateway power off and on.
- Open a browser and go to the gateway configuration address 192.168.88.89/admin.
- Log in with the default admin/admin, or the password you changed, then change it on the Change Password screen if needed.
- Set the BACnet Device Settings. Give the Device ID a value that is unique on the whole BACnet network.
- Press SAVE on every screen where you changed something.
- Confirm Activate Configuration and save. The gateway stores the settings and reboots.
- Record all changes, as the gateway pages can be reached via 192.168.88.89 and the address you set.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 505 and 505D BACnet IP manual, p. 18-19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.