Viessmann Boiler: Connecting Vitodens B2HA with black GUI to the Versatronik 300

Updated · by Aurora Star Tech Inc.

Connecting Vitodens B2HA with black GUI to the Versatronik 300 on a Viessmann boiler: Same CAT5e daisy-chain method as the HO1 version. The boiler needs its outdoor temperature sensor connected, and the boiler coding addresses differ.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200 B2HA with new (black) GUI

How to fix connecting vitodens b2ha with black gui to the versatronik 300: step by step

  1. Plug the CAT5e cable into the J1 receptacle at the upper right of the Versatronik 300 PCB.
  2. Daisy-chain the cable from control to control.
  3. Connect the outdoor temperature sensor. If none is available, use a 10 kOhm resistor (brown-black-orange) to simulate about 77F/25C.
  4. Set the boiler coding addresses listed for the B2HA.
  5. Assign each boiler a unique LON address starting at 1 and counting up.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

704083704092

Source: Versatronik 300 Cascade Control V1.4 manual, p. 17. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.