Viessmann Boiler: Connecting the LON gateway to the boiler control
Connecting the LON gateway to the boiler control on a Viessmann boiler: Wiring and power connections for the Versatronik gateway on the Vitotronic and Vitodens controls. Refer to the manual for the specific boiler control for the LON card location.
Applies to: Vitotronic 100 GC1/GC1B, Vitotronic 300 GW2/GW5B, Vitotronic 200 HO1, Vitodens 200 B2HA, Vitocontrol-S
How to fix connecting the lon gateway to the boiler control: step by step
- Install the LON communication card in the boiler control, as described in that control's manual.
- Plug the supplied 3 ft (91 cm) CAT-5 cable into the RJ45 socket in the control and into the RJ45 socket inside the gateway.
- For Vitodens 200 (WB2B, HO1, B2HA), plug the cable into the boiler with the LON card installed; a longer field-supplied cable may be needed depending on distance.
- Wire the LON 2-wire BMS connection to gateway terminals A and B.
- Power the wall-mount 511 (120VAC) with the plug-in power cord.
- Power the DIN-rail 511D (24VAC) from a field-supplied 24VAC supply.
- For Vitocontrol-S, install the LON card before connecting the gateway.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 511 and 511D LON Type B manual, pp. 8-13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.