Viessmann Boiler: Connect the gateway to a Vitotronic 100 / 300 GW2 / 300 GW5B control
Connect the gateway to a Vitotronic 100 / 300 GW2 / 300 GW5B control on a Viessmann boiler: The gateway links to the control through a CAT-5 cable and sends the LON network out on terminals A and B. The control needs its LON communication card fitted.
Applies to: Vitotronic 100 GC1/GC1B, Vitotronic 300 GW2, Vitotronic 300 GW5B
How to fix connect the gateway to a vitotronic 100 / 300 gw2 / 300 gw5b control: step by step
- Confirm the manual for the boiler control is at hand and the LON communication card is installed in the control.
- Plug the supplied 3 ft (91 cm) CAT-5 cable with RJ45 connectors into the RJ45 socket on the control's LON card.
- Plug the other end into the RJ45 socket inside the Versatronik 501 gateway.
- Wire the LON network to gateway terminals A and B.
- Connect the plug-in 120VAC power cord to the gateway.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 501 & 501D LON gateway manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.