Viessmann Boiler: Choose boiler control method by command state
Choose boiler control method by command state on a Viessmann boiler: Boilers can be driven by a modulation percentage (Boiler On) or by a temperature set point (Auto mode). Pick the command state for each boiler.
Applies to: Boiler 1-16 command state points AO301-316
How to fix choose boiler control method by command state: step by step
- Set command state to 1 to run the boiler on the command value percentage.
- Set command state to -1 (0xFF) to run the boiler on its set point.
- Set command state to 0 to turn the boiler off.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Versatronik 515 and 515D BACIP Type B gateway manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.