Viessmann Boiler: Cascade setup for maximum burner count
Cascade setup for maximum burner count on a Viessmann boiler: To keep as many burners running as possible, set the next-boiler threshold to zero and the minimum modulation to the lowest stage value.
Applies to: Versatronik 200 multi-boiler cascade
How to fix cascade setup for maximum burner count: step by step
- Set Mod % next boiler on to 0.
- Set Modulation Min to the minimum modulation degree of the heat generator stages.
- Check that the boiler on-delay in the burner control matches the controller setting.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Versatronik 200 installation and operating manual, p. 144. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.